2.5MW/5.0MWh BESS SOLUTION

In the field of energy storage, the 2.5MW/5.0MWh Battery Energy Storage System (BESS) solution represents a state-of-the-art integration of technology. Configured to meet project requirements with a 1.25MW/2.5MWh setup, this system utilizes Hoy Power container products. Featuring LFP batteries known for their high safety and performance, the solution comprises multiple battery packs and racks housed in a 20-foot container, achieving a total capacity of 5.505MWh. The following details outline the system’s configuration and technical specifications.

Project Information

According to the requirements, the configuration of the energy storage system is 1.25MW/2.5MWh. The specific configurations for using Hoy Power container product parameters are as follows.

1 Battery information

•  Battery cell specification: LFP battery cell, 3.2V, 280Ah, single capacity is 0.896 kWh.

•  Pack specifications: 153.6V/280Ah, cell connection type 1P48S, the capacity of single Pack is 48 x 0.896 = 43.008kWh.

2 Solution Configuration

• 8pcs battery pack per battery rack: 8 battery pack serially connected plus 1 High Voltage Box; single capacity of battery rack is 8 x 43.008 = 344.064 kWh.

• 8 pcs battery Rack parallel connected as the battery container, total capacity is 8 x 344.064KWh = 2.752 MWh, which are integrated in one 20ft battery container.

• Each battery compartment corresponds to one 1250 kW PCS.

• One PCS is connected to one 1250 kVA step-up transformer.

• PCS Assembly is equipped with two sets of 1250 kW PCS and one set of 2500 kVA step-up transformer.

• The energy storage system includes 2 sets of 20 ft 2.752MWh battery co mpartment, and one set of PCS assembly.

The project total capacity of BESS is 5.505 MWh.

BESS Configuration

System Information
Rated Power2.5MW
Nameplate Capacity(MWh)5.505MWh
Battery System
Battery ChemistryLFP
Type280Ah
Configuration1P48S
Number of Racks8
Number of Modules Per Rack8
Rate voltage(V)1228.8V
Voltage Range(V)1075.2-1382.4V
C Rate0.5P
Degree of ProtectionIP55
Operating Temperature Range(°C) Working Altitude-30°C ~ 60°C
≤2000m
Relative Humidity5~95% (Non condensing)
General Information
CoolingLiquid Cooling
Aux Power Supply400VAC 50HZ 3P4L
Communication ProtocolModbus TCP/IP
Certificate & ComplianceUL9540A, UL1973, IEC62619, CE

Battery System

Maxbo Battery Storage System rely on LFP chemistry to provide stable, industry leading safety and high-power performance. Each cell is 3.2V 280V, the specification as follows.

ItemSpecification
Nominal Voltage280Ah
Nominal Voltage3.2V
Voltage Range2.8-3.6V
Typical Energy896Wh
Dimension173.93*71.55*207.23
Weight5.43
Operation Temperature Range(charging)0°C to 50°C -20°C to 55°C -30°C to 60°C Per month≤3.0%
Operation Temperature Range(discharging)
Storage Temperature
Residual capacity loss
Recommended application≤0.5CP
Rest SOC≥5%
CertificateUL9540A, IEC62619, UL1973

Container Layout

Delivery Scope

No. Equipment Specifications Qty/ Container Unit Total Qty
1 20ft Battery Container Capacity of 2.752MWh, including battery racks, lighting, FSS, control system etc. 1 Pcs 2
1.120ft Container6058(W)*2438(D)*2896(H)mm, C4 standard1Pcs1
1.2Liquid cooling systemLiquid cooling units, liquid cooling pipes, liquid cooling board etc., with capacity of 45kW1Set1
1.3FSS (Fire suppression system)Including smoke detector, temperature detector, combustible gas detector etc., FSS controller, FM200 FSS1Set1
1.4Security SystemFlooding, Access control system1Set1
1.5Battery Racks275.251kWh,2.48t, every rack consist of 8 pcs 1P48S pack, 825(W)*1035(D)*2473(H)mm8Pcs8
1.6BCP
(Battery Combiner Panel)
Including local control system1Pcs1
Power Supply:UPS-3kVA,Power supply time period≥20min
Bus switchgear: 2500A/1500V 4P
Dimension: 600*800*2100mm
Rated Power≥25kW
2 PCS Assembly Rated Power 2500kW,AC output 600V/50Hz, DC input range 915~1500V,Three phase three wire1 Pcs 1
2.1PCS (Power Conversion System)Rated Power 1250kW, AC output 630V/50Hz, DC input range 915~1500V,Three phase three wire1Pcs2
2.2Set-up TransformerDry type, 35±2×2.5%/0.6kV, Dy11,2500kVA1Pcs1
2.3High Voltage Outlet CabinetIncluding high-voltage load switch, fuse, lightning arrester, high-voltage bushing, etc.1Pcs1
2.4Cabinet and spare partsDetermine dimensions based on final design drawings1Set1

 

Published On: August 8th, 2024 / Categories: Design / Tags: /

Related Solutions

Related Blogs

Let’s Make Things Happen

* Please fill in as fully as possible so that we can provide a more accurate proposal.

Add notice about your Privacy Policy here.

Let’s Make Things Happen

The Maxbo team of sales consultants will continue to enrich our own expertise and experience to empower the development of sustainable energy with rigor.


Maxbo CEO

You will need to provide: 1. the amount of electricity used. 2. the type and power of the load. 3. the electricity consumption habits (daytime/nighttime consumption). 4. the need to store electricity. 5. the need to feed electricity to the mains. 6. drawings or address of the installation site. 7. other special requirements

We can provide you with a quotation, a specification for all products, a circuit connection diagram and a diagram of the installation and placement of the PV panels. Any other requirements and adjustments needed can be discussed with our team.

We can meet the needs of most scenarios, whether your application is for domestic, commercial and industrial use, in remote areas, or for grid-level energy storage, we have experienced colleagues to design and deliver the right solution.

* Please fill in as fully as possible so that we can provide a more accurate proposal.

Add notice about your Privacy Policy here.

Title